what size wire to run 700 feet of 120v

Underground electrical service entry (C) Daniel Friedman Hole-and-corner Electrical Service Cable Sizes & Amps Q&A

  • Postal service a QUESTION or Comment almost buried or secret electrical service entry cabling or wiring

InspectAPedia tolerates no conflicts of involvement. We have no relationship with advertisers, products, or services discussed at this website.


FAQs about cached or hole-and-corner electrical service entry cable ampacity & surreptitious electric service ampacity ratings.

Questions & answers on how to determine the size, chapters, or ampacity of electrical service at a building.

This article series explains how to estimate the electric service size, (or "electric ability" or "service amps") at a building past visual examination of the buried service entry cables and other details that are available by simple visual inspection.

Nosotros also provide an ARTICLE INDEX for this topic, or you can try the folio tiptop or bottom SEARCH BOX as a quick way to find information y'all demand.

Cloak-and-dagger & Other SEC Electric Service Wire Size Q&A

These questions & answers well-nigh the sizing of underground electric service entry wires or service laterals were posted originally at Hugger-mugger SERVICE LATERALS - topic habitation - then you volition want to exist sure to see the wire sizing table givent here.

[Click to overstate whatsoever image]

@Deneen, actually you lot are far-more than "clued-in" than people who merely run wires willy-nilly without trying to observe out what is needed.

An underground electric service can exist run in conduit (special pipe used for electrial wiring) or it tin can be run directly if the proper UF or hugger-mugger feeder wire blazon is purchased.

The wire size you need depends on the size of electrical service (chief panel and switch) to be installed; for a small dwelling you'd typically use at least
a 100-Amp rated electric service and console.

The wire size you need is going to be given in electrical codes, selected by your installing electric contractor, based on BOTH the Ampacity (say 100A) and the total wire length - where your length of 150 ft. is pretty long, and is as well described
at
SE Cable & BRANCH Excursion WIRE SIZES vs AMPS

The table of wire sizes I'll show below is excerpted from that web page.

You lot'll see that for 100A the service entry cable is typically a #1 or a #0 gauge wire depending on whether you're using copper (smaller diameter wire) or aluminum wire.

BUT
when running the service entry cable for a longer distance, similar your 150 feet, information technology will be wire size two/0 - copper or four/0 aluminum. (More zeroes is a larger wire size).

Examples of wire sizes for longer runs are also at

SE Cable & WIRE SIZES FOR LONG RUNS https://inspectapedia.com/electric/Long-Run-SEC-Cable-Sizes.php

The wire Blazon you volition demand is one rated for burying underground and volition be marked at to the lowest degree
UF for "Secret Feeder"

At that place are boosted letters and markings that reflect more than wire properties like temperature range;

Watch out: if y'all are not familiar with proper, safe electrical wiring, making a mistake can cause a fire or kill someone. And so be sure you have aid from a qualified electrician. Also in about communities you're required to become an electrical let to do or accept done the work yous draw. The electrical inspector'due south visits and inspections are in that location to assistance keep you and everyone else safe so be sure y'all go those done.

Liquid-tight electrial conduit for wiring -f rom Southwire cited & discussed at Inspectapedia.com

What size of and type of conduit and service wire do I need for a small home, we are burring information technology secret from electric meter to home around 150 ft.i am a female that is totally clueless about these things. I need help

Ineed to know what size of service wire. And conduit I need for service from meter to home. I am burring information technology hugger-mugger. From meter to home around 100 ft

Todd

SE CABLE SIZES FOR LONG WIRE RUNS - SEE THIS Commodity for wire size for long runs

https://inspectapedia.com/electric/Long-Run-SEC-Cable-Sizes.php

I need to run underground wire 300 ft. to a motel with a 150 amp console from my barn. What type and size wire volition I need?

Normally yeah;

Does the underground power company wiring size need to be changed when going from 100 to 200 amp service?

I accept a 250 foot run from the primary pole to the meter box. I accept a 225 amp breaker box. What gauge wire practise I demand for the primary run and the meter to breaker box?

Tim

Check out

SE CABLE SIZES FOR LONG WIRE RUNS - SEE THIS ARTICLE for wire size for long runs

at https://inspectapedia.com/electric/Long-Run-SEC-Cable-Sizes.php

and don't hesitate to enquire if that leaves you lot with questions

Thank you

I'm putting underground electric service to my house. I have 200 amp service. I demand 200 feet of underground. What size wire exercise I demand.

Online calculator for electrical wire size depending on length and amps - at Inspectapedia.comGreg

Using the online calculator itself cited at the article I'll cite merely below to support a 200A load at the finish of the run

you lot'd meet an acceptable (under 3%) voltage driblet of 2.lxxx% with 350 kcmil wire

Illustration: edited from output from Southwire'south voltage drop reckoner at southwire.com

[Click to enlarge any prototype]

I accept a 650' run from the service pole and I'm non sure with the voltage drop what size wire is needed for a 200 amp service.

Daryll

Be sure you have the necessary permits, approvals, inspections as that will assistance your installation be safe.

See SE CABLE & WIRE SIZES FOR LONG RUNS for help with wire sizing.

I'm replacing a onetime box with new 200 amp box and running 300 foot to new trailer tin can anyone requite me any advice

Need to run a 200 amp service from pole to new house, 800' underground. What size wire?

What sz of direct burial wire for 200 amp service, 200' abroad coming from on the basis transformer?

Need to comport 100 amps 500 anxiety. What size under ground wire practice I need

Sad 400 feet under ground

What size wire do I Need to go 400 feet for a 200 amp service?

200amp service at 300ft underground what size wire do I need

I have a 150 amp service I need to run 200 feet of wire what size wire practise I need

I accept a 200 foot run to a 200 amp household service. I am doing clandestine. What size wire do i need?

A new self-protected transformer, xv kVA, 34.5/nineteen.9Kv 120/240 V was recently installed 520 anxiety from my domicile in Costa rica. The elec. utility insists that the meter be installed at the street. I want to run underground cable directly up to my house (with a 100 amp service). What size AL cable will I need?

Anon

At the ARTICLE INDEX encounter the live links for

SE Cable SIZES vs AMPfor more wire size guidelines

SIZE of WIRE REQUIRED for receptacle circuits and like wiring situations

And beware: you lot'll need an individual disconnect and fuse protection (breakers) for both of those services.

We have 400amp service split with 200amp to firm with quick disconnect. The other 200amp volition go to our barn and workshop of the other quick disconnect. My question is what size al wire should we use for 230' run to barn? It will be hush-hush 3" pic. What size quad 250 or 350?? Thanks

Mike

Using Southwire'due south voltage drop calculator, for 100A service and a 250 ft. run single phase, 240VAC, aluminum SEC buried,

1 conductors per phase utilizing a #3/0 Aluminum conductor volition limit the voltage driblet to ii.82% or less when supplying 100.0 amps for 250 feet on a 240 volt system.

If nosotros change the voltage to 120VAC the result is: 1 conductors per stage utilizing a #400 Aluminum usher will limit the voltage drop to two.94% or less when supplying 100.0 amps for 250 feet on a 120 volt organisation.

Typically, the maximum allowed voltage drib for residential installations is 3% that's why I chose that number. You can see you'd be ok with direct buried three/0 Al.

You may want to run your wire in 3" conduit - double check with what your local electrical utility volition accept.

Check out the definition of VDI - voltage drop index, and likewise "Maximum Wire Length vs Wire Size & Circuit Amps" at SE Cable SIZES vs AMPS inspectapedia.com/electric/Electrical_SEC_Sizes_Amps.php and of course get to UF (underground feeder) rated wire.

what size of hush-hush wire exercise I need to run a 100 amp service, 250 feet away?

You are always safe for going to the adjacent larger size or diameter wire for a longer run. So since a 15 amp circuit would use 14 guess wire you could get up to number 12 wire. Be certain you're using the proper wire type for undercover feeder.

I need to run 300 feet from out to panel to run 110volt motor off a xv amp billow... What estimate wire do I need?

Going to upgrade to a 200 amp service. Going to run from pole transformer to house breaker panel 150 feet underground. 120 volts. What cablevision size and conduit is required.

Sure Mike

Yous didn't specify voltage but I assume you meant 240V. At 208V yous'd need bigger wires and at 120V much much bigger wires.

At that place are many wire sizing tables online and in the NEC, and some reasonable online wire size calculators

Generally I found that for 200A at 450 ft and 240V yous need to use 300 MCM copper wire or 500 MCM aluminum wire.

You'll want to cheque again the NEC tables and UF notes.

see http://www.jhlarson.com/

Can you provide wiring size data for 200 amp underground service with a 450 foot run.

Thanks

...

Go on reading at UNDERGROUND SERVICE LATERALS - topic habitation or select a topic from the closely-related articles below, or see the complete Article INDEX.

Or encounter these

Articles on Edifice Electrical Service Wiring - SEC Cabling

  • AMPS VOLTS Conclusion - home
  • Electric INSPECTOR SAFETY PROCEDURES
  • Electric WIRE TYPES CODES USES
  • SERVICE ENTRY WIRING & AMPACITY - home
    • ELECTRICAL SERVICE ENTRY DAMAGE
    • SE CABLE & BRANCH CIRCUIT WIRE SIZES vs AMPS
    • SE CABLE & WIRE SIZES FOR LONG RUNS - SEE THIS Commodity for wire size for long runs
    • SERVICE AMPACITY
    • SERVICE DROP
    • SERVICE GROUNDING DEFECTS
    • Hush-hush SERVICE LATERALS
  • SIZE of WIRE REQUIRED for ELECTRICAL RECEPTACLES

Suggested commendation for this web page

UNDERGROUND SERVICE LATERAL FAQs at InspectApedia.com - online encyclopedia of edifice & ecology inspection, testing, diagnosis, repair, & trouble prevention communication.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to Electrical INSPECTION & TESTING

Or use the SEARCH BOX found below to Inquire a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Questions & answers or comments nigh cached or underground electrical service entry cabling or wiring.

Attempt the search box just below, or if yous prefer, post a question or comment in the Comments box beneath and we volition respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may exist delayed: if your annotate contains an image, spider web link, or text that looks to the software as if it might be a spider web link, your posting will appear later information technology has been approved by a moderator. Apologies for the delay.

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman

westthenowearce.blogspot.com

Source: https://inspectapedia.com/electric/Underground-Electrical-Service-FAQs.php